EURODIM TWIN TECH
Page 90 sur 92
9.1 PROCEDURE TO BE FOLLOWED IN THE EVENT OF AN ERROR
Errors list
Action
Downgraded mode
r, s, t phase error
− Verify the external network
− Verify the connections on the
cabinet
− Verify the main breaker in the
cabinet
− Verify the CTRL fuses
The modules connected on
the faulty phase are no
longer useable.
Fan 1, 2, 3 error
− Proceed with replacing the
cabinet’s faulty fan
Risk of an increase in the
temperature inside the
cabinet. See temperature
error.
Controller error
− Switch the cabinet off/on at the
mains to remove the error,
where applicable
− Switch to the controller (if
present) using the cabinet
selector
− Stop the cabinet and proceed
with replacing the controller
Communication error
− Verify the connections between
the TTD HUMAN INTERFACE
(HMI) and the cabinet
TTD HUMAN INTERFACE
(HMI) will no longer be
synchronised with this
controller
24 V, 9 V, 9 V control and
1V2 error
− Switch to the controller (if
present) using the cabinet
selector
− Stop the cabinet and proceed
with replacing the controller
Temperature error
− Refresh the room temperature
(See chapter cabinet fan)
Automatic reduction of the
circuit control value until
the temperature is
acceptable