ADB Eurodim Twin Tech handleiding

96 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 92 van 96
EURODIM TWIN TECH
Page 90 sur 92
9.1 PROCEDURE TO BE FOLLOWED IN THE EVENT OF AN ERROR
Errors list
Action
Downgraded mode
r, s, t phase error
Verify the external network
Verify the connections on the
cabinet
Verify the main breaker in the
cabinet
Verify the CTRL fuses
The modules connected on
the faulty phase are no
longer useable.
Fan 1, 2, 3 error
Proceed with replacing the
cabinet’s faulty fan
Risk of an increase in the
temperature inside the
cabinet. See temperature
error.
Controller error
Switch the cabinet off/on at the
mains to remove the error,
where applicable
Switch to the controller (if
present) using the cabinet
selector
Stop the cabinet and proceed
with replacing the controller
Communication error
Verify the connections between
the TTD HUMAN INTERFACE
(HMI) and the cabinet
TTD HUMAN INTERFACE
(HMI) will no longer be
synchronised with this
controller
24 V, 9 V, 9 V control and
1V2 error
Switch to the controller (if
present) using the cabinet
selector
Stop the cabinet and proceed
with replacing the controller
Temperature error
Refresh the room temperature
(See chapter cabinet fan)
Automatic reduction of the
circuit control value until
the temperature is
acceptable

Bekijk gratis de handleiding van ADB Eurodim Twin Tech, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkADB
ModelEurodim Twin Tech
CategorieVerlichting
TaalNederlands
Grootte19177 MB